65
Reference Manual
00809-0200-4420, Rev HB
Appendix C: DeltaV Ready
January 2015
Figure C-2. Decommissioned Nodes Folder within DeltaV Explorer
Commission the Gateway using the following procedure:
1. Select START>PROGRAMS>DELTAV>ENGINEERING> DELTAV EXPLORE to launch the
DeltaV Explorer application.
2. Expand the folder SYSTEM CONFIGURATION >PHYSICAL
NETWORK>DECOMMISSIONED NODES.
3. Right click on the Smart Wireless Gateway and select Commission.
4. Enter a name for the Gateway and select OK.
5. Select YES when prompted to Auto-Sense Wireless Gateway.
At this time the Reconcile I/O window will appear. The purpose of this screen is to assign
WirelessHART devices to DeltaV I/O channel. This allows the wireless device to be referenced in
other DeltaV applications like Control Studio.
Figure C-3. Assign WirelessHART Devices to DeltaV I/O Channel
Comments to this Manuals