Section 5: Host Integration
January 2015
Host Integration
Unmapped parameter read response?: This is the value returned by the Gateway if the
Ethernet/IP master requests a register with no data assigned to it (empty register). It is
recommended this be set to zero fill to prevent errors.
Parameter mapping
Register Mapping is the process of assigning data points from wireless field devices to
Ethernet/IP registers. These registers can then be read by a Ethernet/IP master or client.
Ethernet/IP register mapping can be found by navigating to System Settings>Protocols>
EtherNet/IP>EtherNet/IP Member Map.
Figure 5-8. Ethernet/IP Register Map Page
Table 5-4. Summary of Terms Used for the Ethernet/IP Mapping Page
Terms Description
Input Instance Ethernet/IP Input Static Assembly Instance - 496 bytes
Output Instance Ethernet/IP Output Static Assembly Instance - 496 bytes
Member Ethernet/IP Instance Member in which data will get produced or consumed
Point Name Assigned data point in the format HARTtag.parameter
New entry Creates a new entry in this table
<<First Navigates to the first page of this table
<<Previous Navigates to the previous page of this table
Search Finds the next occurrence of the characters entered into this field