69
Reference Manual
00809-0200-4420, Rev HB
Appendix D: Redundancy
January 2015
Figure D-2. Redundancy Status
After the redundancy system settings have been configured, the two Gateways must be
connected and undergo a pairing process.
To pair both Gateways and form a redundant system:
1. Connect a PC/laptop to the primary Ethernet port on Gateway A.
2. Log in using the admin user account.
3. Navigate to Diagnostics>Advanced>Redundancy Status.
4. Connect the secondary Ethernet port on Gateway A to the secondary Ethernet port on
Gateway B (see Figure D-3 on page 70, Redundancy Setup Connections).
5. A dialog will appear on the page; select Form redundant pair.
6. Wait for the Pairing to redundant peer status to turn green.
7. Select Return to page.
Comments to this Manuals